UHA-Series Axial Fan Tubular Unit Heaters

General Technical Data

Input/Output•Electrical & Air•Sizes & Weights•Power

Input/Output

Model
30
45
60
75
100
125
150
175
200
225
250
300
350
400
Total Input [Btu/h]x[1000]
30
45
60
75
100
125
150
175
200
225
250
300
350
385
Total Output [Btu/h]x[1000]
24.6
36.9
49.2
61.5
82
1.02.5
123
143.5
164
184.5
205
246
288.6
315.7
Efficiency
82% for all models
Number of Burners
2
3
4
5
6
7
7
8
9
10
11
12
14
14
Number of Axial Fans
1
1
1
1
1
1
1
1
1
1
1
2
2
2
Gas Connection [in]
3/8
3/8
1/2
1/2
1/2
1/2
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
Inlet Pressure - ([in wc] NG Min.)
5 - All Models
Inlet Pressure - (LPG Propane Min.)
12 - All Models
Inlet Pressure - (NG & LP Propane Max.)
14 - All Models

back to top

Electrical & Air

Model
30
45
60
75
100
125
150
175
200
225
250
300
350
400
Electrical Supply
115 V / 60 Hz / 10 - All Models
Full Load Amps @ 115 V
3.0
3.0
4.1
4.1
5.8
5.8
7.1
7.1
10.6
10.6
10.6
11.6
11.6
11.6
Air Volume [CFM]
691
691
1376
1376
1902
1902
2245
2245
3716
3716
3716
4663
4663
4663

back to top

Sizes & Weights

Model
30
45
60
75
100
125
150
175
200
225
250
300
350
400
Recomended Max Mounting Height [ft]
12
12
15
15
20
20
20
20
25
25
25
30
30
30
Axial Fan Diameter [in]
10
10
16
16
16
16
16
16
19.7
19.7
19.7
16
16
16
Flue Size [in]
4 - All Models
Combustion Air Size [in]
4
4
4
4
4
4
4
4
4
4
4
5
5
5
Weight [lb]
65
70
85
90
105
110
205
225
255
265
270
355
375
375

back to top

Power

Model
30
45
60
75
100
125
150
175
200
225
250
300
350
400
Horsepower
.06
.06
.08
.08
.2
.2
.2
.2
.3
.3
.3
.4
.4
.4
Fan Motor Amps @ 115 V
1.8
1.8
2.6
2.6
4.3
4.3
4.3
4.3
4.7
4.7
4.7
8.6
8.6
8.6
Fan Motor RPM
1630
1630
1030
1030
1175
1175
1200
1200
1085
1085
1100
1155
1155
1155
Fan Motor Type
SP
SP
SP
SP
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC

back to top

Installation Code and Annual Inspections:
All installations and service of BANANZA® products must be performed by a contractor qualified in the installation and service of products sold and supplied by Bananza and conform to all requirements set forth in the BANANZA® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Bananza recommends that a qualified contractor annually inspect your BANANZA® products and perform service where necessary, using only replacement parts sold and supplied by Bananza.

Further Information:
Applications, engineering and detailed guidance on systems design, installation and product performance is available through BANANZA® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

BANANZA® products are not for residential use.

BANANZA® documents are intended to assist licensed professionals in the exercise of their professional judgement.