BH-Series Low-Intensity Infrared Heaters

General Technical Data

Tube Lengths•Inputs•Weights•General Info•Clearances to Combustibles



Tube Lengths

Model
40 60 80 100 115 125 140 150 175 200
Min. Straight Tube Length
10 20 20 30 30 40 40 50 50 60
Min. U-Tube Length
N/A 11,17 11,17 16,7 16,7 21,7 21,7 26,7 26,7 31,7
Overall Min. Tube Length
10,11 20,11 20,11 30,11 30,11 40,11 40,11 50,11 50,11 60,11
Overall Min. U-Tube Length
N/A 12,6 12,6 17,6 17,6 22,6 22,6 27,6 27,6 32,6
* For additional lengths, please see the current Installation, Operation and Service Manual
back to top

Inputs

Model
40 60 80 100 115 125 140 150 175 200
Inlet Pressure (NG min)
4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 5 5
Inlet Pressure (LPG Propane min)
11 11 11 11 11 11 11 11 11 11
Inlet Pressure (NG & LPG Propane max)
14 14 14 14 14 14 14 14 14 14
Gas Connect (NPT)
½" ½" ½" ½" ½" ½" ¾" ¾" ¾" ¾"

back to top

Weights

Tube & Accessory Pkg. Length (ft)
10 20 30 40 50 60 70 80
Hot Rolled or Aluminized Tube w/ Alum. Reflector (lb)
52 86 120 161 206 240 281 322
Aluminized Tube w/ Stainless Reflector (lb)
66 113 152 208 265 304 360 416
Burner
29
Alumn. U-Tube w/ Alumn. End Caps
19
Alumn. U-Tube w/ Stainless End Caps
20


back to top

General Information

Fuel
NG or LPG Propane
Electrical Supply
120V,60Hz,1A
Heat Exchanger Tube
10 ft Sections, 4" dia, 16 Gauge, First 10 ft ALUMI-THERM® Steel Tubing [Remaining Hot Rolled or Heat Treated Aluminized Tubing]
Exhaust Flue (dia.)
4"
Reflector and End Caps
.024 Aluminum [Optional - .024 Stainless Steel Type 304]
Control System
Fully Automatic, Three-Try, 100% Shut-Off, Direct Spark Electronic Ignition Control
Approved as
Indoor (Vented or Unvented)
Certification
ANSI Z83.20/CSA 2.34, 2.17, 2.20
Warranty
Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)

back to top

Clearances to Combustables (in.)

Model
40
60
80
100
115/125
140/150
175/200
*
Hrz.
45°
Hrz.
45°
Hrz.
45°
Hrz.
45°
Hrz.
45°
Hrz.
45°
Hrz.
45°
A
6
8
6
8
6
8
6
10
6
10
6
12
8
12
B
27
8
35
8
38
8
40
8
46
8
50
8
52
8
C
52
50
62
59
65
65
70
73
76
77
79
83
82
85
D
27
46
35
54
38
60
40
64
46
69
50
74
52
79
back to top

Installation Code and Annual Inspections:
All installations and service of BANANZA® products must be performed by a contractor qualified in the installation and service of products sold and supplied by Bananza and conform to all requirements set forth in the BANANZA® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Bananza recommends that a qualified contractor annually inspect your BANANZA® products and perform service where necessary, using only replacement parts sold and supplied by Bananza.

Further Information:
Applications, engineering and detailed guidance on systems design, installation and product performance is available through BANANZA® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

BANANZA® products are not for residential use.

BANANZA® documents are intended to assist licensed professionals in the exercise of their professional judgement.