BMA-Series
Indirect Fired Air Handling Units

General Technical Data

Capacity by Model Number Chart•CFM Capacity Graph•Internal Static Pressure Graph

Capacity by Model Number Chart

Output (MBH) Input (MBH) CFM
Model
Max Min Max Min Blower Size Max Min Flue Size
35
350 240 435 300 (1)15x15 6,000 3,500 6"
45
450 240 560 300 (1)15x15 6,000 3,500 6"
50
500 240 630 300 (2)12x12 8,000 4,000 6"
65
650 520 810 640 (2)12x12 8,000 4,000 6"
75
750 520 940 650 (2)15x15 12,000 6,000 6"
85
850 520 1,060 650 (2)15x15 12,000 6,000 8"
100
1,000 520 1,250 650 (2)15x15 12,000 6,000 8"
125
1,250 560 1,565 700 (2)18x18 18,000 10,000 10"
150
1,500 560 1,880 700 (2)20x20 24,000 13,000 12"
175
1,750 600 2,190 750 (2)20x20 24,000 13,000 12"
200
2,000 600 2,500 750 (2)25x25 37,000 21,000 14"
225
2,250 600 2,800 750 (2)25x25 37,000 21,000 14"
250
2,500 600 3,130 750 (2)25x25 45,000 21,000 14"
275
2,750 720 3,440 900 (2)25x25 45,000 21,000 14"
300
3,000 720 3,750 900 (2)25x25 45,000 30,000 14"
350
3,500 720 4,380 900 (2)30x30 57,000 35,000 16"
400
4,000 1,400 5,000 1,750 (2)30x30 57,000 35,000 16"
450
4,500 1,400 5,600 1,750 (2)30x30 57,000 35,000 16"

back to top

Percentage of CFM Capacity Graph



back to top

Internal Static Pressure Graph



back to top

Installation Code and Annual Inspections:
All installations and service of BANANZA® products must be performed by a contractor qualified in the installation and service of products sold and supplied by Bananza and conform to all requirements set forth in the BANANZA® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Bananza recommends that a qualified contractor annually inspect your BANANZA® products and perform service where necessary, using only replacement parts sold and supplied by Bananza.

Further Information:
Applications, engineering and detailed guidance on systems design, installation and product performance is available through BANANZA® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

BANANZA® products are not for residential use.

BANANZA® documents are intended to assist licensed professionals in the exercise of their professional judgement.